May 27, 2015 Safety Alert 6-15 Inspections and Compliance Directorate Washington, DC

This Safety Alert is being issued due to recent safety concerns discovered on vessels with fixed CO2 fire fighting systems. It is critical that operators of vessels with fixed CO2 systems are familiar with the operation of the systems; conduct periodic inspections of the systems for readiness, and know the signs for detecting when a discharge has occurred. It is recommended that the appropriate crew members receive training on CO2 system operation and its basic components.

Recently, during the annual servicing of a KIDDE CO2 system onboard a passenger ferry, a technician and Coast Guard Marine Inspector discovered that an undetected discharge of the CO2 system within the emergency generator room had taken place. Although the time of the inadvertent discharge could not be determined, the cause was due to be a worn internal mechanism within the control head.

The crew was unaware of the discharge in the emergency generator room because the space did not require any indicators (e.g., alarm, smoke/heat detection) to alert the crew and nobody was present at the time of discharge. This circumstance presented three latent unsafe conditions: the failure could have occurred while someone was within the space, a person could have entered the space after the release and the space remained unprotected for an unknown period of time.

Due to the risks associated with an inadvertent discharge of a fixed CO2 system, the Coast Guard strongly recommends that owners and operators ensure that appropriate vessel personnel:

• Receive adequate training to perform routine inspections of their vessel’s fixed CO2 systems and fully understand their operation, particularly those protecting large spaces or multiple areas,

• Frequently review and update operating manuals, checklists, and safety management systems associated with vessel extinguishing systems onboard, and

• Post clear instructions for fixed CO2 system emergency operation.

This safety alert is provided for informational purposes only and does not relieve any domestic or international safety, operational or material requirement. Developed by the Sector Southeastern New England – Prevention Department. For questions or concerns, please email LT Kelli Dougherty – Kelli.M.Dougherty@uscg.mil. Distributed by the Office of Investigations and Casualty Analysis, Washington DC.

About the Author

Documentation
Documentation
administrator

IMPORTANT LINKS: FOIA | USA.gov | U.S. Department of Homeland Security | DHS Office of Inspector General | WhiteHouse.gov | MHS Notice of Privacy Practices

Unitedstatesvessel.us is a privately owned document preparation service that is not operated by any government agency.